template: ferroamp-energyhub
products:
- brand: Ferroamp
description:
generic: EnergyHub
capabilities: ["battery-control"]
requirements:
description:
de: |
Modbus TCP muss vom Installateur oder vom Ferroamp-Support für den EnergyHub freigeschaltet werden.
Die Schnittstelle ist ausschließlich über die Ethernet-Schnittstelle des EnergyHub erreichbar.
Die Netzwerte werden über die externen Stromwandler (CTs) am Netzanschlusspunkt gemessen.
en: |
Modbus TCP has to be enabled for the EnergyHub by the installer or Ferroamp support.
The interface is only reachable via the EnergyHub's Ethernet interface.
Grid values are measured by the external current transformers (CTs) at the grid connection point.
params:
- name: usage
choice: ["grid", "pv", "battery"]
- name: modbus
choice: ["tcpip"]
port: 502
id: 1
- preset: battery-minmaxsoc
- preset: battery-power
- name: maxchargepower
required: true
- name: maxdischargepower
required: true
render: |
type: custom
{{- if eq .usage "grid" }}
power:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 3100 # Grid Active Power (kW)
type: input
decode: float32s
scale: 1000
energy:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 3068 # Energy Imported From Grid (kWh)
type: input
decode: float32s
returnenergy:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 3064 # Energy Exported To Grid (kWh)
type: input
decode: float32s
currents:
- source: modbus
{{- include "modbus" . | indent 4 }}
register:
address: 3112 # Grid Active Current L1 (Arms)
type: input
decode: float32s
- source: modbus
{{- include "modbus" . | indent 4 }}
register:
address: 3116 # Grid Active Current L2 (Arms)
type: input
decode: float32s
- source: modbus
{{- include "modbus" . | indent 4 }}
register:
address: 3120 # Grid Active Current L3 (Arms)
type: input
decode: float32s
voltages:
- source: modbus
{{- include "modbus" . | indent 4 }}
register:
address: 2032 # Grid Voltage L1 (Vrms)
type: input
decode: float32s
- source: modbus
{{- include "modbus" . | indent 4 }}
register:
address: 2036 # Grid Voltage L2 (Vrms)
type: input
decode: float32s
- source: modbus
{{- include "modbus" . | indent 4 }}
register:
address: 2040 # Grid Voltage L3 (Vrms)
type: input
decode: float32s
{{- end }}
{{- if eq .usage "pv" }}
power:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 5100 # Solar Output Power (kW)
type: input
decode: float32s
scale: 1000
energy:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 5064 # Energy produced (kWh)
type: input
decode: float32s
{{- end }}
{{- if eq .usage "battery" }}
# Input and holding registers are separate address spaces: 6064 reads charged energy as
# input but writes "Battery Power Reference" as holding, likewise 6000.
power:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 6100 # Battery Output Power (kW), negative implies charging
type: input
decode: float32s
scale: 1000
# The spec labels 6064 as discharge and 6068 as charge, but the device does the
# opposite: 6064 accumulates while charging and the lifetime totals only yield a
# plausible round-trip efficiency this way round.
energy:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 6068 # discharged energy (input, kWh)
type: input
decode: float32s
returnenergy:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 6064 # charged energy (input, kWh)
type: input
decode: float32s
soc:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 6016 # State of Charge (%)
type: input
decode: float32s
capacity:
source: modbus
{{- include "modbus" . | indent 2 }}
register:
address: 6008 # Rated capacity of all connected batteries (kWh)
type: input
decode: float32s
# Battery Mode 0 hands control back to the EnergyHub's own optimization, mode 1 follows
# Battery Power Reference. The reference has to be written before the mode. Setpoints are
# given in W and scaled to the register's kW unit.
batterymode:
source: switch
switch:
- case: 1 # normal
set:
source: sequence
set:
# mode first: it hands control back immediately and makes the stale reference
# inert, so a failed second write cannot leave the battery stuck
- source: const
value: 0 # default mode
set:
source: modbus
{{- include "modbus" . | indent 10 }}
register:
address: 6000 # Battery Mode (holding)
type: writemultiple
encoding: uint16
- source: const
value: 0 # clear the setpoint left over from a forced charge
set:
source: modbus
{{- include "modbus" . | indent 10 }}
register:
address: 6064 # Battery Power Reference (holding, kW)
type: writemultiple
encoding: float32s
scale: 0.001
- case: 2 # hold
set:
source: sequence
set:
- source: const
value: 0 # neither charge nor discharge
set:
source: modbus
{{- include "modbus" . | indent 10 }}
register:
address: 6064 # Battery Power Reference (holding, kW)
type: writemultiple
encoding: float32s
scale: 0.001
- source: const
value: 1 # power mode
set:
source: modbus
{{- include "modbus" . | indent 10 }}
register:
address: 6000 # Battery Mode (holding)
type: writemultiple
encoding: uint16
- case: 3 # charge
set:
source: sequence
set:
- source: const
value: {{ mul .maxchargepower -1 }} # negative implies charging
set:
source: modbus
{{- include "modbus" . | indent 10 }}
register:
address: 6064 # Battery Power Reference (holding, kW)
type: writemultiple
encoding: float32s
scale: 0.001
- source: const
value: 1 # power mode
set:
source: modbus
{{- include "modbus" . | indent 10 }}
register:
address: 6000 # Battery Mode (holding)
type: writemultiple
encoding: uint16
{{- include "battery-minmaxsoc" . }}
{{- include "battery-power" . }}
{{- end }}