package obis // OBIS codes for electricity meters. // https://www.kbr.de/de/obis-kennzeichen/elektrizitaet // // Names use Import (+A, OBIS channel 1/2x) and Export (-A, channel 2/2x) for // active power and energy. Energy registers carry an optional tariff suffix // T1/T2 (OBIS field E). // // The OBIS D field selects how the value is processed: // - D=7 instantaneous momentary sample ("now") -> unqualified // - D=4 current average running mean over the ongoing demand -> Demand suffix // period (a meter-configured window, e.g. 15 min) // - D=5 last average mean over the last completed period // - D=8 time integral cumulative energy -> Energy* // Active power (kW) const ( PowerImport = "1-0:1.7.0" // instantaneous +A PowerExport = "1-0:2.7.0" // instantaneous -A PowerImportL1 = "1-0:21.7.0" PowerImportL2 = "1-0:41.7.0" PowerImportL3 = "1-0:61.7.0" PowerExportL1 = "1-0:22.7.0" PowerExportL2 = "1-0:42.7.0" PowerExportL3 = "1-0:62.7.0" PowerImportDemand = "1-0:1.4.0" // current average +A PowerExportDemand = "1-0:2.4.0" // current average -A PowerImportDemandL1 = "1-0:21.4.0" PowerImportDemandL2 = "1-0:41.4.0" PowerImportDemandL3 = "1-0:61.4.0" ) // Active energy (kWh) const ( EnergyImport = "1-0:1.8.0" // +A, total EnergyImportT1 = "1-0:1.8.1" // +A, tariff 1 EnergyImportT2 = "1-0:1.8.2" // +A, tariff 2 EnergyExport = "1-0:2.8.0" // -A, total EnergyExportT1 = "1-0:2.8.1" // -A, tariff 1 EnergyExportT2 = "1-0:2.8.2" // -A, tariff 2 ) // Current (A) const ( CurrentL1 = "1-0:31.7.0" // instantaneous CurrentL2 = "1-0:51.7.0" CurrentL3 = "1-0:71.7.0" CurrentDemandL1 = "1-0:31.4.0" // current average CurrentDemandL2 = "1-0:51.4.0" CurrentDemandL3 = "1-0:71.4.0" ) // Voltage (V) const ( VoltageL1 = "1-0:32.7.0" // instantaneous VoltageL2 = "1-0:52.7.0" VoltageL3 = "1-0:72.7.0" VoltageDemandL1 = "1-0:32.4.0" // current average VoltageDemandL2 = "1-0:52.4.0" VoltageDemandL3 = "1-0:72.4.0" )