evcc-io/templates/definition/meter/sma-datamanager.yaml

84 lines
2 KiB
YAML

template: sma-data-manager
covers:
- sma-data-manager-m-lite
products:
- brand: SMA
description:
generic: Data Manager
requirements:
description:
de: In der Weboberfläche des SMA Data Manager muss im Bereich "Externe Kommunikation" der Schalter "Modbus Server aktivieren" eingeschaltet sein.
en: In the web interface of the SMA Data Manager you need to activate "Modbus Server activated" in the section "External communication".
params:
- name: usage
choice: ["grid", "pv", "battery"]
allinone: true
- name: host
- name: port
default: 502
render: |
type: custom
{{- if eq .usage "pv" }}
power:
source: modbus
uri: {{ .host }}:{{ .port }} # Port 502
id: 2
register:
address: 30775 # PV, W
type: holding
decode: int32nan
{{- end }}
{{- if eq .usage "grid" }}
power:
source: calc
add:
- source: modbus
uri: {{ .host }}:{{ .port }} # Port 502
id: 2
register:
address: 31503 # L1, W
type: holding
decode: int32nan
- source: modbus
uri: {{ .host }}:{{ .port }} # Port 502
id: 2
register:
address: 31505 # L2, W
type: holding
decode: int32nan
- source: modbus
uri: {{ .host }}:{{ .port }} # Port 502
id: 2
register:
address: 31507 # L3, W
type: holding
decode: int32nan
{{- end }}
{{- if eq .usage "battery" }}
power:
source: calc
add:
- source: modbus
uri: {{ .host }}:{{ .port }} # Port 502
id: 2
register:
address: 31393 # Battery charge, W
type: holding
decode: uint32nan
scale: -1
- source: modbus
uri: {{ .host }}:{{ .port }} # Port 502
id: 2
register:
address: 31395 # Battery dis-charge, W
type: holding
decode: uint32nan
soc:
source: modbus
uri: {{ .host }}:{{ .port }} # Port 502
id: 2
register:
address: 30845 # Battery Soc, %
type: holding
decode: uint32nan
{{- end }}