template: atmoce
|
|
products:
|
|
- brand: Atmoce
|
|
description:
|
|
generic: MG100 M-gateway
|
|
capabilities: ["battery-control"]
|
|
requirements:
|
|
description:
|
|
de: |
|
|
Unterstützung für Atmoce MG100 (im Lieferumfang von MC100 und MC100-T enthalten). Erfordert, dass der Installateur Modbus TCP in der Konfiguration aktiviert; verfügbar ab Firmware-Version 01.01.00.18.10.
|
|
en: |
|
|
Support for Atmoce MG100 (included with MC100 and MC100-T). Requires installer to enable Modbus TCP in configuration; available in firmware 01.01.00.18.10 or later.
|
|
params:
|
|
- name: usage
|
|
choice: ["grid", "pv", "battery"]
|
|
- name: modbus
|
|
choice: ["tcpip"]
|
|
id: 1
|
|
- name: maxacpower
|
|
- preset: battery-params
|
|
- name: capacity
|
|
service: modbus/read?address=60031&type=holding&encoding=uint32&scale=0.001&resulttype=int&{modbus}
|
|
- name: minsoc
|
|
advanced: true
|
|
default: 10
|
|
- name: maxsoc
|
|
advanced: true
|
|
default: 100
|
|
render: |
|
|
type: custom
|
|
{{- if eq .usage "grid" }}
|
|
power:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60073 # Grid Active Power (kW * 1000)
|
|
type: holding
|
|
decode: int32
|
|
scale: 1
|
|
energy:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60184 # Cumulative Electricity Purchase Volume (kWh * 100)
|
|
type: holding
|
|
decode: uint64
|
|
scale: 0.01
|
|
returnenergy:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60178 # Cumulative Electricity Sales Volume (kWh * 100)
|
|
type: holding
|
|
decode: uint64
|
|
scale: 0.01
|
|
currents:
|
|
- source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60090 # Phase A Grid Current (A * 100)
|
|
type: holding
|
|
decode: int16
|
|
scale: 0.01
|
|
- source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60092 # Phase B Grid Current (A * 100)
|
|
type: holding
|
|
decode: int16
|
|
scale: 0.01
|
|
- source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60094 # Phase C Grid Current (A * 100)
|
|
type: holding
|
|
decode: int16
|
|
scale: 0.01
|
|
voltages:
|
|
- source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60089 # Phase A Grid Voltage (V * 10)
|
|
type: holding
|
|
decode: uint16
|
|
scale: 0.1
|
|
- source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60091 # Phase B Grid Voltage (V * 10)
|
|
type: holding
|
|
decode: uint16
|
|
scale: 0.1
|
|
- source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60093 # Phase C Grid Voltage (V * 10)
|
|
type: holding
|
|
decode: uint16
|
|
scale: 0.1
|
|
{{- end }}
|
|
{{- if eq .usage "pv" }}
|
|
power:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60069 # Photovoltaic Power Output (kW * 1000)
|
|
type: holding
|
|
decode: uint32
|
|
scale: 1
|
|
energy:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60160 # Cumulative Photovoltaic Power Generation (kWh * 100)
|
|
type: holding
|
|
decode: uint64
|
|
scale: 0.01
|
|
maxacpower: {{ .maxacpower }}
|
|
{{- end }}
|
|
{{- if eq .usage "battery" }}
|
|
power:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60071 # Energy Storage Charging/Discharging Power (kW * 1000)
|
|
type: holding
|
|
decode: int32
|
|
scale: 1
|
|
energy:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60172 # Cumulative Energy Storage Discharging Capacity (kWh * 100)
|
|
type: holding
|
|
decode: uint64
|
|
scale: 0.01
|
|
returnenergy:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60166 # Cumulative Energy Storage Charging Capacity (kWh * 100)
|
|
type: holding
|
|
decode: uint64
|
|
scale: 0.01
|
|
soc:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 2 }}
|
|
register:
|
|
address: 60095 # Energy Storage SOC (%)
|
|
type: holding
|
|
decode: uint16
|
|
scale: 1
|
|
batterymode:
|
|
source: switch
|
|
switch:
|
|
- case: 1 # normal
|
|
set:
|
|
source: const
|
|
value: 2
|
|
set:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 8 }}
|
|
register:
|
|
address: 60310 # Energy Storage Forced Charging/Discharging (0 = Forced charging, 1 = Forced discharging, 2 = Exit forced charging/discharging, 99 = Pause)
|
|
type: writemultiple
|
|
decode: uint16
|
|
- case: 2 # hold -> Pause charge/discharge
|
|
set:
|
|
source: const
|
|
value: 99
|
|
set:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 8 }}
|
|
register:
|
|
address: 60310 # Energy Storage Forced Charging/Discharging (0 = Forced charging, 1 = Forced discharging, 2 = Exit forced charging/discharging, 99 = Pause)
|
|
type: writemultiple
|
|
decode: uint16
|
|
- case: 3 # charge -> Enable grid charging with maximum target soc (will be stopped by evcc)
|
|
set:
|
|
source: sequence
|
|
set:
|
|
- source: const
|
|
value: {{ .maxsoc }}
|
|
set:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 10 }}
|
|
register:
|
|
address: 60312 # Energy Storage Forced Charging/Discharging Target SOC
|
|
type: writemultiple
|
|
decode: uint16
|
|
- source: const
|
|
value: 0
|
|
set:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 10 }}
|
|
register:
|
|
address: 60311 # Energy Storage Forced Charging/Discharging Mode (0 = Target SOC, 1 = Charging/discharging duration)
|
|
type: writemultiple
|
|
decode: uint16
|
|
- source: const
|
|
value: 0
|
|
set:
|
|
source: modbus
|
|
{{- include "modbus" . | indent 10 }}
|
|
register:
|
|
address: 60310 # Energy Storage Forced Charging/Discharging (0 = Forced charging, 1 = Forced discharging, 2 = Exit forced charging/discharging, 99 = Pause)
|
|
type: writemultiple
|
|
decode: uint16
|
|
{{- include "battery-params" . }}
|
|
{{- end }}
|